top of page

12-32 Zone conventional fire alarm panel is designed based on EN54 part 2&4 standard.

 

12-32 Zone Fire alarm control Panel Features

  • modularized design, the panel can expend from 1 zone to 32 zones easily
  • 2 level control mode by a lock
  • 24VDC and 5VDC power supply output.
  • FIRE and FAULT signal output.
  • 2 general sounders output.
  • Each zone has 1 circuit detectors input.
  • Each zone can be disable by a button.
  • SILENCE button to stop BUZZER and SOUNDERS.
  • EVACUATE button to start a manual fire alarm immediately
  • battery low protection function, when battery voltage lower than 21VDC,battery will be cut off automatically until the mains power is on
  • an optional GSM module for fire alarm by SMS
     
    TEM4-32 Zone panel
    Model No.AW-CFP2166-04-32
    Mains supply voltage110VAC or 240VAC
    Internal power supply27.2VDC
    Total output current limited3A@240VAC
    Batteries (Default Configuration)12V2AH*2-24VDC in Total
    End of Line device6.8k Q2,5% tolerance, 0.25W (color code-blue, grey, red, gold)
    End of line resistor value6.8k Q2,5% tolerance, 0.25W (color code-blue, grey, red, gold)
    Dimensions(mm)362*565*124mm
    Weight (without batteries8kg
    Weight (with batteries)12.5kg
    EnvironmentalClass A temperature range: -5 to 50°C
    Humidity: 5 to 95% RH, non-condensing

12-32 Zone Fire Alarm Control Panel

  • 12-32 Zone conventional fire alarm panel is designed based on EN54 part 2&4 standard.

  • AW-CFP2166-12-32

bottom of page