1 Zone conventional fire alarm panel is designed based on EN54 part 2&4 standard.

It is the heart of the fire automatic alarm system, which can realize centralized control,

can supply power to the detectors, manual call point, bell etc.

One zone of the panel can match with 20 pieces fire alarm system accessories.

The 1 Zone fire alarm panel has the following characteristics:

  • Analogue conventional detector inputs: 20 detectors or MCPs maximum.
  • Smaller size and easier for installation, but all-around.
  • Maximum number of bells per CIE: 4 Bells.
  • relay-outputs: FIRE/FAULT.
  • High-capacity batteries: 12V2.3Ah*2, over 8h for stand-by use.
  • Automatic power switchover: mains power and stand-by power.
  • Succinct functional buttons: friendly user interface for easy operation and recognition.
  • Fault supervision and notification: inputs, sounder, mains/batteries.
  • Evacuation: man-made fire alarm condition on panel.
  • Silence: sounders and panel buzzer.
  • Extensible application for GSM: inform user anytime by mobile telephone.
     
    AC INPUT 220VAC 50/60Hz
      
    DC OUTPUT24VDC typical
    Voltage for MCU5V for MCU
    Current at 24VDC from PSE450mA standby current
    Maximum current from PSE1A except batteries charge
    Batteries current1.85A maximum, current limited
     
    Auxiliary output
    24VDC +/- 10%, 100 mA max,
    current limited, monitored
     
    Batteries
    2*12V/ 2.3Ah sealed lead acid gel,
    self-regulated *
    Battery low-voltage protection21V
    Detectors connection allowed each zone20 (except MCPs)
    Zone alarm current6mA minimum/ 27mA maximum
    Sounder output2*0.75A maximum
    Fire Relay1A/30VDC maximum
    Fault Relay1A/30VDC    maximum
    Communication protocol2 wires RS485 bus system
    EOL resistor for zone6.8K 1W
    EOL resistor for outputs6.8K 1W
    Fuse for AC Power1 A/ 250V glass tube fuse 5 X 20mm
    Fuse on DC Power1A/ 250V glass tube fuse 5 X 20mm
     EnvironmentalClass A temperature range: -5 to 50°C 
    Humidity: 5 to 95% RH, non-condensing
     Terminal blocks ratingAll terminals rated for 12 to18 AWG
    (0.75 to 2.5 mm2)

1 Zone Fire Alarm Control Panel

  • 1 Zone fire alarm panel is the heart of the conventional fire alarm system, which can realize centralized control, can supply power to the smoke detectors.

  • AW-CFP2166-1